Generator Sets
Tier II - 13 to 460 kW |
|
John Deere powered generator sets built for dependable performance in emergency or prime power applications. Economical to run and sized to meet the needs of the private or commercial user.
John Deere quality backed by John Deere warranty and service.
TIER 2 SPECIFICATIONS
STANDARD 60 HERTZ / 1800 RPM RATINGS
Note: The (kVA) Calculated Rating Range is determined by a 0.8 power factor
Engine
Model |
Rating |
Engine
Power |
Calculated
Electrical Power |
Engine
Specs |
Performance
Curve |
| |
|
(hp) |
(kW) |
(kW) |
(kVA) |
|
|
4024TF270 |
Prime |
43 |
32 |
27 |
33.8 |
|
|
Standby |
48 |
36 |
30 |
37.5 |
5030TF270 |
Prime |
72 |
54 |
45 |
56.3 |
|
|
Standby |
80 |
60 |
50 |
62.5 |
5030HF270 |
Prime |
87 |
65 |
55 |
68.8 |
|
|
Standby |
96 |
72 |
60 |
75 |
3029TF270 |
Prime |
59 |
44 |
37-38 |
46-48 |
|
|
Standby |
64 |
48 |
40-42 |
50-52 |
4045TF275 |
Continuous |
85 |
64 |
54-56 |
67-70 |
|
|
Prime |
102 |
76 |
64-66 |
79-83 |
Standby |
113
|
84 |
70-73 |
88-92 |
4045HF275 |
Continuous |
107 |
81 |
68-71 |
85-88 |
|
|
Prime |
131 |
98 |
82-85 |
102-107 |
Standby |
145 |
108 |
90-94 |
113-118 |
4045HF275 |
Continuous |
107 |
81 |
68-71 |
85-88 |
|
|
Prime |
142 |
106 |
87-92 |
109-115 |
Standby |
157 |
117 |
97-102 |
121-128 |
4045HF475 |
Continuous |
142 |
107 |
89-94 |
112-117 |
|
|
Prime |
174 |
130 |
107-112 |
134-141 |
Standby |
192 |
143 |
119-124 |
148-156 |
6068TF275 |
Continuous |
127 |
96 |
80-84
|
100-105 |
|
|
Prime |
150 |
112 |
93-97
|
116-122 |
Standby |
165 |
123 |
103-108 |
129-134 |
6068HF275 |
Continuous |
152 |
115 |
96-101 |
120-126 |
|
|
Prime |
200 |
149 |
124-130 |
155-162 |
Standby |
220 |
164 |
137-143 |
171-179 |
6068HF275 |
Continuous |
197 |
149 |
125-130 |
156-163 |
|
|
Prime |
228 |
170 |
141-148 |
177-185 |
Standby |
250 |
187 |
156-163 |
195-204 |
6068HF275 |
Continuous |
197 |
149 |
125-130 |
156-163 |
|
|
Prime |
256 |
191 |
159-166 |
198-207 |
Standby |
282 |
210 |
176-184 |
219-229 |
6068HF475 |
Continuous |
220 |
166 |
139-145 |
173-181 |
|
|
Prime |
286 |
213 |
177-185 |
221-231 |
Standby |
314 |
234 |
196-205 |
245-256 |
6081HF070 |
Continuous |
275
|
205 |
169-177 |
211-221 |
|
|
Prime |
295
|
220 |
182-190 |
228-238 |
Standby |
347
|
259 |
217-226 |
271-283 |
6081HF070 |
Continuous |
275
|
205 |
167-175 |
209-219 |
|
|
Prime |
353 |
263 |
218-228 |
273-285 |
Standby |
413 |
308 |
258-269 |
322-336 |
6125HF070 |
Continuous |
402 |
300 |
249-261 |
311-326 |
|
|
Prime |
402 |
300 |
249-261 |
312-326 |
Standby |
442 |
330 |
276-288 |
345-361 |
6125HF070 |
Continuous |
425 |
317 |
263-275 |
329-344 |
|
|
Prime |
439 |
327 |
272-285 |
340-356 |
Standby |
483 |
360 |
301-315 |
376-394 |
6125HF070 |
Continuous |
425 |
317 |
260-272 |
325-340 |
|
|
Prime |
512 |
382 |
318-332 |
397-415 |
Standby |
563 |
420 |
351-367 |
439-459 |
6125HF070 |
Continuous |
425 |
317 |
264-276 |
330-345 |
|
|
Prime |
512 |
382 |
323-337 |
404-421 |
Standby |
617 |
460 |
393-411 |
491-514 |
Estimated
Dimensions (inches)
| |
 |
| MODEL |
Height
(H) |
Length
(L) |
Width
(W) |
4045D |
56 |
72 |
40 |
4045T |
56 |
72 |
40 |
6068T |
56 |
84 |
40 |
6081T |
60 |
96 |
40 |
6081A |
60 |
100 |
40 |
6081H |
72 |
108 |
44 |
6125A |
72 |
130 |
50 |
6125H |
72 |
130 |
50 |
Standard
Equipment:
- John Deere engine
AC brushless generator w/ 1% regulation
Unit mounted circuit breaker
3 to 5% mechanical generator
Radiator cooling system with 110° F ambient rating(minimum)
Vibration isolated, unit mounted control panel with
AC voltmeter, AC ammeter, AC frequency meter, selector
switch, start/stop control, oil pressure, engine coolant,
and elapsed time meter gauges
Automatic shutdown for high coolant temperature and
low lube oil pressure
Dry type air cleaner
Industrial silencer
- Complete unit mounted on structural steel base
Optional
Equipment:
- Automatic controls
Transfer switches
Remote and customized instrument panels
Trailer mounted
Enclosures (weather-proof & sound attenuated)
Heavy duty air cleaners
Special grade silencers
Trickle chargers
Batteries
Fuel Tanks
- Other options available, please inquire.
|
|
|
|
|
|
|
|
 |
TESTIMONIALS: |
I attended the Tier 3 training at Bell Power. Tim Stevens was an excellent instructor that went above and beyond to ensure that we left the class with as much knowledge as possible. The training is going to be a huge asset to our company with the introduction of the new Tier technology. After leaving, I felt that I was 100% comfortable with all of the new technology that will come along with the increased emissions standards. The training that we received is irreplaceable considering all of the changes that the new emissions standards are going to have on our industry. I felt challenged all week and that most of the information was new to me. At the end of each day I felt I walked away from the training with more knowledge and experience on these new engines. I was extremely impressed with the level of training that we received. Bell Power was an excellent host and I was impressed with the presentation, training aids, and hands on time that was used in training. Thanks again!
Steve Sabol, Shop Foreman
Keystone Pump and Power, Dillsburg, PA
|
| |
 |
|
|
|
|
|
| |
|
|
|
| |
|